Grid synchronization of power converters using multiple second order generalized integrators
Article 2008 en
Abstract
1 min read
This paper presents a new frequency-adaptive synchronization method for grid-connected power converters which allows estimating not only the positive- and negative-sequence components of the power signal at the fundamental frequency, but also other sequence components at higher frequencies. The proposed system is called the MSOGI-FLL since it is based on a decoupled network consisting of multiple second order generalized integrators (MSOGI) which are frequency-adaptive by using a frequency-locked loop (FLL). In this paper, the MSOGI-FLL is analyzed and its performance is evaluated by both simulations and experiments.
Discussion(0)
No comments yet. Be the first to comment.