Grid-Current-Feedback Active Damping for <italic>LCL</italic> Resonance in Grid-Connected Voltage-Source Converters
Article 2015 en
Abstract
1 min read
This paper investigates active damping of LCL-filter resonance in a grid-connected voltage-source converter with only grid-current feedback control. Basic analysis in the s-domain shows that the proposed damping technique with a negative high-pass filter along its damping path is equivalent to adding a virtual impedance across the grid-side inductance. This added impedance is more precisely represented by a series RL branch in parallel with a negative inductance. The negative inductance helps to mitigate phase lag caused by time delays found in a digitally controlled system. The mitigation of phase-lag, in turn, helps to shrink the region of nonminimum-phase behavior caused by negative virtual resistance inserted unintentionally by most digitally implemented active damping techniques. The presented high-pass-filtered active damping technique with a single grid-current feedback loop is thus a more effective technique, whose systematic design in the z-domain has been developed in this paper. For verification, experimental testing has been performed with results obtained matching the theoretical expectations closely.